The compressed air precooler is a specialized product developed for certain industries (such as air oxygen production, nitrogen production, and gas membrane processes) that require a low gas dew point and an outlet gas temperature of around 5°C.

Process flow diagram



Technical Parameters:

  • Gas inlet pressure: 0.2–6.4 MPa
  • Gas inlet temperature: ≤45°C
  • Gas outlet temperature: 3–10°C
  • Pressure drop: ≤0.01 MPa
  • Refrigerant: R-22 or, per customer request, R134a, R407C, R404a, R507, or other fluorine-free environmentally friendly refrigerants
  • Operating voltage: 220V or 380V
  • Cooling water temperature: ≤32°C
  • Inlet water pressure: 0.15–0.4 MPa

Product Features:

  • The refrigeration compressor uses brands such as Panasonic (Japan), Haili, Tecumseh (USA), Copeland, Danfoss Performer, Maneurop, HANBELL (Taiwan), RefComp (Italy), BITZER (Germany), offering long service life, high energy efficiency, stable operation, low noise, and reliable performance. Protection level is IP54 (dust and splash proof).
  • Refrigeration control components use products from DANFOSS (Denmark), SPORLAN (USA), EMERSON (USA), ensuring reliability and excellent performance.
  • Electrical components are from Schneider (France), Siemens (Germany), Delixi, and other reputable brands.
  • Features include automatic thermal compensation under light load, overcurrent, overload, and high/low refrigerant pressure protection.
  • Heat exchangers are high-efficiency shell-and-tube or plate-type, offering high heat transfer efficiency, compact size, and a tight structure.
  • Float-type or electronic timer drain devices with anti-clogging design prevent blockages.
  • Enclosed box structure with heat-sprayed surface, aesthetically pleasing and rust-resistant.
  • No foundation required, stable operation without vibration, low maintenance, no consumables, low operating costs, easy operation, and continuous operation without dedicated supervision.
  • Dynamic display of working parameters for clear, intuitive monitoring.

Model Specifications and Performance Parameters

Model / Item
XS-180AYLXS-360AYLXS-600WYLXS-960WYLXS-1200WYLXS-1500WYLXS-1800WYLXS-2400WYLXS-3000WYLXS-3600WYLXS-4800WYLXS-7000WYLXS-9000WYLXS-12000WYLXS-13800WYL
Nominal volumetric flow rate(m3/h)1803606009601200150018002400300036004800700090001200013800
Compressor Power(KW)1.22.342.565.807.509.0010.5312.4015.4019.3623.330.751.46373
Air Inlet/Outlet DiameterDN40DN50DN65DN80DN100DN100DN125DN125DN150DN150DN150DN200DN250DN300DN350
Cooling Water Circulation Volume(m3/h)Air CoolingAir Cooling3.55.17.28.710.31315182028426070
Cooling Water Pipe Diameter--RC11/2"RC11/2"RC11/2"RC11/2"RC11/2"RC2"RC2"RC21/2″RC21/2"DN80DN100DN125DN125
Equipment Weight(KG)100180350580700880120014001700200024803100370040004500